Communications parameters (Common serial options)
The data transfer rate, parity type, inverter ID number and communication error trip time can be
changed from the operation panel or the computer on the network.
Title Function Adjustment range Default setting
H
Communication baud rate 0: 1200bps
1: 2400bps
2: 4800bps
3: 9600bps
4:19200bps
3
H Parity (Common serial) 0: Non (non parity)
1: Even (even parity)
2: Odd (odd parity)
1
H Inverter number
099
0
H Communication error trip
time
0: Disabled
1100 (sec)
0
*: Disabled・・・Means that the inverter will not trip even if a communication error occurs.
Trip・・・・・・・Means that the inverter will trip if a time-out occurs.
If a time-out occurs, the error message “GTT” will blink on the display panel.
6.16.1 Using RS232C/RS485 conversion units
Setting up the communications function
Commands (RUN/STOP commands) entered across a network have priority (over commands
from the operation panel or terminal boards).
Data transmission specifications
Item Specifications
Data transmission
scheme
Half-duplex
Connection scheme Centralized control
Synchronization
scheme
Asynchronous
Data transfer rate Default: 9600 baud (parameter setting)
Selectable from among 1200, 2400, 4800, 9600 and 19200 baud
Character
transmission
ASCII mode ... JIS X 0201, 8-bit (fixed, ASCII)
Binary code ... Binary code, 8-bit (fixed)
Stop bit length Receive (inverter): 1bit, Send (inverter): 2 bits
Error detection Parity: Selectable among Even, Odd and Non by parameter setting,
Check sum method
Character
transmission format
Receiving: 11-bit, Sending: 12-bit
Order of bit
transmission
Lower-order bits first
Frame length Variable to a maximum of 17 bytes
Examples of connection for RS485 communications
<Example of connection>
Optional unit
Host computer
nC1 nC1 nC1 nC1 nC1
・・・・
・・・・
Optional unit