Installation
24 975-0171-01-01
Connecting the AC Output Wires
To make the AC output wiring connections:
1. Remove one of the AC knockouts from the front or side of the unit. Do not
leave the knockout inside the wiring compartment.
2. Install a strain-relief clamp in the AC knockout and run the AC wiring
through the strain-relief clamp.
3. Strip approximately 2 inches (50 mm) off the jacket from the AC cable and
separate the wires.
4. Using a 1/4" blade slot screwdriver, loosen the terminal screws on the AC
output terminals. Do not remove the screws.
5. Connect the line and neutral wires to the output terminals (labeled AC
Output on the terminal block, Figure 5 on page 22) as follows:
6. Tighten the terminal screws. Leave some slack wire inside the wiring box.
7. Connect the ground wires to a free position on the ground bus, Figure 5 on
page 22. If solid ground wire is being used, the wire can be connected directly
under the screw heads. If stranded ground wire is being used, ring terminals
must also be used.
8. Secure the strain-relief clamp on the AC output cable jacket.
9. Attach the wiring compartment cover panel and tighten the four screws.
10. Connect the outgoing AC wires to an AC load panel equipped with circuit
breakers.
CAUTION: Risk of equipment damage
Do not connect the output of the inverter to any incoming AC source.
Important:
The applicable installation code may not allow you to run the AC
input and AC output wiring through the same AC knockout.
Terminals
Line for Dual
Output
Lines for Single
Output
N Neutral 2 Unused
L2 Line 2 Unused
N Neutral 1 Neutral
L1 Line 1 Line