V. Removal and Replacement of Components
WARNING
• This unit should be diagnosed and repaired only by qualied service personnel to
reduce the risk of death, electric shock, serious injury, or re.
• Move the power switch to the "OFF" position, then unplug the unit from the
electrical outlet before servicing.
CHOKING HAZARD: Ensure all components, fasteners, and thumbscrews are
securely in place after the unit is serviced. Make sure that none have fallen into
the storage bin.
• Make sure all food zones in the icemaker and storage bin are clean after the
unit is serviced. For cleaning procedures, see "VI.B. Cleaning and Sanitizing
Instructions."
A. Service for Refrigerant Lines
WARNING
• Repairs requiring the refrigeration circuit to be opened must be performed by
properly trained and EPA-certied service personnel.
• Use an electronic leak detector or soap bubbles to check for leaks. Add a trace of
refrigerant to the system (if using an electronic leak detector), and then raise the
pressure using nitrogen gas (140 PSIG). DO NOT use R-134a as a mixture with
pressurized air for leak testing.
NOTICE
• Always recover the refrigerant and store it in an approved container. Do not
discharge the refrigerant into the atmosphere.
• Do not leave the system open for longer than 15 minutes when replacing or
servicing parts. The Polyol Ester (POE) oils used in R-134a units can absorb
moisture quickly. Therefore it is important to prevent moisture from entering the
system when replacing or servicing parts.
• Always install a new drier every time the sealed refrigeration system is opened. Do
not replace the drier until after all other repair or replacement has been made.
• When brazing, protect the drier by using a wet cloth to prevent the drier from
overheating. Do not allow the drier to exceed 250°F (121°C).
1. Refrigerant Recovery
No refrigerant access valves are provided on this unit. Using proper refrigerant
practices, utilize a temporary tap-line valve on the high side to recover the refrigerant.
Store the refrigerant in an approved container. Do not discharge the refrigerant into the
atmosphere.
After recovery is complete, replace the tap-line valve with a proper, permanent access
valve.