Outback Power Systems GFX1448E Marine Battery User Manual


 
Specifications
900-0112-01-00 Rev B 49
Table 19 48-Volt Inverter Settings (MATE)
Field Item Default Minimum Maximum
search sensitivity (see page 14 for increments)
6 0 50
search pulse length
8 4 20
Search
search pulse spacing
60 AC cycles 4 AC cycles 120 AC cycles
ac transfer control Grid Grid or Gen
ac1/grid limit
25 Aac 2.5 Aac 30 Aac
Input
ac2/gen limit
25 Aac 2.5 Aac 30 Aac
low battery cut-out (LBCO)
42 Vdc 36 Vdc 48 Vdc
low battery cut-in (LBCI)
50 Vdc 40 Vdc 56 Vdc
Inverter
adjust output voltage
230 Vac 210 Vac 250 Vac
charger limit
5.5 Aac 0 Aac 6 Aac
absorb voltage
57.6 Vdc 52 Vdc 64 Vdc
absorb time limit
1.0 hours 0.0 hours 24.0 hours
float voltage
54.4 Vdc 48 Vdc 60 Vdc
float time period
1.0 hours 0.0 hours 24.0 hours
refloat voltage
50 Vdc 48 Vdc 52 Vdc
equalization voltage
58.4 Vdc 56 Vdc 68 Vdc
Charger
equalization time period
1.0 hours 0.0 hours 24.0 hours
ac1/grid lower limit
208 Vac 140 Vac 220 Vac
ac1/grid upper limit
252 Vac 250 Vac 280 Vac
ac1/grid input limit
25 Aac 2.5 Aac 30 Aac
Grid
ac1/grid transfer delay
6 AC cycles 0 AC cycles 240 AC cycles
gen input connect delay
0.5 minutes 0.2 minutes 15 minutes
ac2/gen lower limit
208 Vac 140 Vac 220 Vac
ac2/genupper limit
252 Vac 250 Vac 280 Vac
ac2/gen input limit
25 Aac 2.5 Aac 30 Aac
ac2/gen transfer delay
6 AC cycles 0 AC cycles 240 AC cycles
Generator
(Gen)
ac2/gen support ON ON or OFF
aux output control AUTO ON, OFF, or AUTO
aux output function Cool Fan
Cool Fan, DivertDC, DivertAC, AC Drop, Vent
Fan, Fault, GenAlert, LoadShed, or Remote
genalert on voltage
44 Vdc 40 Vdc 56 Vdc
genalert on delay
4 minutes 0 minutes 240 minutes
genalert off set point
56 Vdc 48 Vdc 72 Vdc
genalert off delay
9 minutes 0 minutes 240 minutes
load shed off voltage
44 Vdc 40 Vdc 56 Vdc
vent fan on set point
52 Vdc 40 Vdc 64 Vdc
vent fan off period
5 minutes 0 minutes 30 minutes
diversion on voltage
58.4 Vdc 48 Vdc 64 Vdc
Auxiliary
(AUX)
diversion off delay
30 seconds 0 seconds 240 seconds
Stacking
stack phase Master Master, OB Slave L1, 3p Classic B, 3p Classic C
master adjust only
0 0 7
Power
Save
slave adjust only
1 1 15
sell re volts
52 Vdc 40 Vdc 60 Vdc
grid tie window User IEEE or User
Sell
grid tie authority GridTie GridTie or No Sell
vac input adjustment
5
236 220 254
vac output adjustment
5
236 220 254
Calibration
(Cal)
battery vdc adjustment
6
2 0 4
5
These values are in digital counts, not volts. Lower counts stand for higher voltages, and higher counts mean lower voltages. One count equals approximately
1 Vac. The range of adjustment is 15 Vac above nominal and 17 Vac below nominal.
6
These values are in digital counts, not volts. One count equals 0.4 Vdc. The range of adjustment is 0.8 Vdc above or below nominal.