7. Assign the PC a static IP address such that the first three segments are the
same as the default IP address, and the last segment is different from the
default IP address.
For example, 169.254.0.xxx, where xxx differs from the last segment of the
default IP address.
Enter 255.255.255.0 into the subnet mask field.
For Windows 7 users, you must enter the IP address of the meter into the
Default Gateway field.
8. Configure the meter. See “Configuring the Meters” on page 7 for configuration
instructions.
9. Remove power. Use a properly rated voltage sensing device to confirm power is
off.
10.If you wish to lock the configuration parameters, remove the inner cover and
move the programming switches (SW1) to the OFF (up) position.
11.Re-install the inner cover.
12.Connect the LAN Ethernet cable if present.
13.Re-install the outer cover.
14.Restore power.
NOTE: All PowerLogic meters have a default IP address of 169.254.0.10 in the
absence of a DHCP service.
Network Connection Ethernet Requirements
To connect the PowerLogic meter to the network:
1. Turn off power to the meter with the installed breaker or disconnecting device.
Use a properly rated voltage sensing device to confirm power is off.
2. Remove the outer cover.
3. If you are changing parameters that require the programming switch to be on,
remove the inner cover and ensure the programming switches are in the ON
position.
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
Apply appropriate personal protective equipment (PPE) and follow
safe electrical work practices. See NFPA 70E.
This equipment must only be installed and serviced by qualified
electrical personnel.
Turn off all power supplying this equipment before working on or
inside equipment.
Always use a properly rated voltage sensing device to confirm
power is off.
Replace all devices, doors and covers before turning on power to
this equipment.
The meters must be connected to the sense voltage and control
voltage through a properly rated disconnect.
Failure to follow these instructions will result in death or serious
injury.