9.2.3 Compliance with Peripheral devices
Use the UL listed fuses at connecting to power supply.
Refer to the instruction manual about selecting the rating of them.
Short circuit test is performed under the condition of the power supply short-circuit currents in
below.
These currents and fuse currents depend on the drive motor capacities.
Table 4. AIC and fuse
Voltage class
Capacity of
applicable
motor (kW)
Inverter model
AIC
(Interrupting
capacity)
Maximum
input
voltage (V)
Fuse class and
currents (A)
0.1 VFNC1S-1001P AIC 1000A 120 CC/J 6 max
0.2 VFNC1S-1002P AIC 1000A 120 CC/J 8 max
0.4 VFNC1S-1004P AIC 1000A 120 CC/J 12 max
Single-phase
100V class
0.75 VFNC1S-1007P AIC 1000A 120 CC/J 22 max
0.2 VFNC1S-2002P(L) AIC 1000A 240 CC/J 4 max
0.4 VFNC1S-2004P(L) AIC 1000A 240 CC/J 8 max
0.75 VFNC1S-2007P(L) AIC 1000A 240 CC/J 12 max
1.5 VFNC1S-2015P(L) AIC 5000A 240 CC/J 22 max
Single-phase
200V class
2.2 VFNC1S-2022P(L) AIC 5000A 240 CC/J 30 max
0.1 VFNC1-2001P AIC 1000A 240 CC/J 3 max
0.2 VFNC1-2002P AIC 1000A 240 CC/J 3 max
0.4 VFNC1-2004P AIC 1000A 240 CC/J 5 max
0.75 VFNC1-2007P AIC 1000A 240 CC/J 8 max
1.5 VFNC1-2015P AIC 5000A 240 CC/J 15 max
Three-phase
200V class
2.2 VFNC1-2022P AIC 5000A 240 CC/J 20 max
Table 5. Power supply short-circuit current and input voltage
Input voltage Drive motor Power supply short-circuit current and maximum input voltage
100V Up to 0.75 kW
Suitable For Use On A Circuit Capable Of Delivering Not More Than 1,000A rms
Symmetrical Amperes, 120 Volts Maximum When Protected by CC/J Class Fuses.
Up to 0.75 kW
Suitable For Use On A Circuit Capable Of Delivering Not More Than 1,000A rms
Symmetrical Amperes, 240 Volts Maximum When Protected by CC/J Class Fuses.
200V
1.5 kW and over
Suitable For Use On A Circuit Capable Of Delivering Not More Than 5,000A rms
Symmetrical Amperes, 240 Volts Maximum When Protected by CC/J Class Fuses.
9.2.4 Motor thermal protection
Selects the electronic thermal protection characteristics that fit with the ratings and characteristics
of the motor. In case of multi motor operation with one inverter, thermal relay should be connected
to each motor.