Toshiba Single-phase 100V class 0.1 to 0.75kW Marine Battery User Manual


 
E6581090
J-2
10
Selection of wiring devices
Non-fuse circuit breaker (MCCB)
Earth leakage breaker (ELCB)
Magnetic contactor
(MC)
Overload relay
(THR)
Without reactor With DC reactor Without reactor With DC reactor
Voltage
class
Capacity of
applicable
motor
(kW)
Inverter model
Rated
current
(A)
Type
MCCB /
(ELCB)
Note1)
Rated
current
(A)
Type
MCCB /
(ELCB)
Note1)
Rated
current
(A)
Type
Note1)
Rated
current
(A)
Type
Note1)
Adjusted
current
(A)
(For reference)
Type
Note1)
0.1 VFNC1S-1001P 5 --- --- 13 --- --- 0.7
0.2 VFNC1S-1002P 10 --- --- 13 --- --- 1.3
0.4 VFNC1S-1004P 15 --- --- 13
CA13
--- --- 2.3
Single-
phase
100V
class
0.75 VFNC1S-1007P 30
NJ30E
(NJV30E)
--- --- 19 CA20 --- --- 3.6
0.2 VFNC1S-2002P(L) 5 5 13 13 1.3
0.4 VFNC1S-2004P(L) 10 5 13 13 2.3
0.75 VFNC1S-2007P(L) 15 10 13
CA13
13 3.6
1.5 VFNC1S-2015P(L) 20 15 19 CA20 13
CA13
6.8
Single-
phase
200V
class
2.2 VFNC1S-2022P(L) 30
NJ30E
(NJV30E)
30
NJ30E
(NJV30E)
26 CA25 19 CA20 9.3
0.1 VFNC1-2001P 5 5 13 13 0.7
0.2 VFNC1-2002P 5 5 13 13 1.3
0.4 VFNC1-2004P 5 5 13 13 2.3
0.75 VFNC1-2007P 10 5 13 13 3.6
1.5 VFNC1-2015P 15 10 13 13 6.8
Three-
phase
200V
class
2.2 VFNC1-2022P 20
NJ30E
(NJV30E)
15
NJ30E
(NJV30E)
13
CA13
13
CA13
9.3
TH13U
Note 1:Produced by Toshiba Industrial Products Sales Corporation.
Note 2:Be sure to attach a surge killer to the exciting coil of the relay and the magnetic contactor.
Note 3:When using the auxiliary contacts 2a of the magnetic contactor MC for the control circuit, connect the
contacts 2a in parallel to increase reliability.