EEC3 System Manual
14
B. Start Interlock
C. Power Inputs
D. Engine Room Checks
E. Trolling Valve (if equipped)
3.1
3.2
3.3
Turn System ON (see Operators Quick Reference Guide).
Verify at the main station various functions: Warm up, Slow, Troll, Sync.
Transfer control to other stations (see Operators Quick Reference Guide) and verify
proper operation of functions at each station.
5.1
To verify separate power inputs, turn ON individual breakers one at a time and verify
that DC power (12 or 24 VDC) is supplied to the Control Processor.
6.1
Gear Operation — Verify that transmission solenoid valves are turning ON and OFF as
you move Control Handles into and out of gear. Make sure that transmission shifts into
appropriate direction — pushing handle forward causes forward boat motion, etc.
7.1
4.1
4.2
4.3
4.4
Move Starboard Control Handle out of NEUTRAL position. Attempt to start engine.
(NOTE: Be prepared to immediately shutdown engine if start interlock has been
wired incorrectly!)
Engine should NOT start; if it does, start interlock has not been wired correctly. Fix
wiring and re-check.
Move Starbord Control Handle back to NEUTRAL position. After handle is moved to
NEUTRAL position, then try to start engine. Engine should start.
Perform same check for Port engine.