2. M-NET CONTROL
2-4-3-1. MA remote controller, Single-refrigerant-system, No System Controller
Original switch setting of the outdoors, indoors, controllers and LMAP at shipment is as follows.
Outdoor unit : Address: 00, CN41: U (Jumper), DipSW2-1: OFF
Indoor unit : Address: 00
ME remote controller : Address: 101
LMAP : Address: 247, CN41: U (Jumper), DipSW1-2: OFF
DipSW2-1(Outdoor) : When the System Remote Controller is used, all the Dip SW2-1 at the outdoor units should be
set to "ON".
* Dip SW2-1 remains OFF when only LMAP03U is used.
DipSW1-2(LMAP) : When the LMAP is used together with System Remote Controller, DipSW1-2 at the LMAP
should be set to "ON".
CN40/CN41 : Change jumper from CN41 to CN 40 at outdoor control board will activate central transmission
power supply to TB7;
(Change jumper at only one outdoor unit when activating the transmission power supply
without using a power supply unit.)
Change jumper from CN41 to CN 40 at LMAP will activate transmission power supply to LMAP
itself;
Power supply unit is recommended to use for a system having more than 1 outdoor unit,
because the central transmission power supply from TB7 of one of outdoor units is risking that
the outdoor unit failure may let down the whole system controller system.
Factory setting
Setting at the site
2-4-3. System examples
1. Outdoor units OC and OS in one refrigerant circuit system are automatically detected.
OC and OS are ranked in descending order of capacity. If units are the same capacity, they are ranked in ascending order
of their address.
2. No address setting is needed.
3. For a system having more than 16 indoor unit, confirm the need of Booster at 2-3 "System configuration restrictions".
NOTE:
Indoor unit
MA R/C MA R/C MA R/C
(Main) (Sub)
MA R/C
SRU
Wireless R/C
*3
*3 For Wireless R/C and Signal receiver unit (SRU), channel 1, 2 and 3 are selectable and should be set to same channel.
*3
*1
To *1 or *2
*2
00 00 00 00 00
TB15
TB5 TB5TB5 TB5 TB5
TB15 TB15 TB15 TB15
Group 2Group 1 Group 3 Group 4
<Two outdoor units>
<One outdoor unit>
TB3TB3
0000
OC OS
PUHY-HP-TSJMU
TB3
00
OC
CN41CN40CN41CN40 CN41CN40