Mitsubishi Electronics H2iSD-1 Marine Battery User Manual


 
H2iSD-36
2010 Hyper-heating Y-SERIES SYSTEM DESIGN (Sept. 2010)
2010 H2i
®
Y-SERIES
SYSTEM DESIGN
4. OUTDOOR INSTALLATION
Safety strap
Provided by others
Important!
For all roof top
installations, safety
straps must be
attached between the
hood(s) and the unit
mounting structure.
Additional Rooftop Mounting Guidelines
Ground-level installation is preferred for outdoor units that include a low
ambient kit. If ground-level installation is not possible, follow general, as
well all additional installation guidelines for rooftop mounting. If you have
any questions, please contact your distributor.
Note:
Low ambient hood(s) increase the overall height of the outdoor
units and make them more susceptible to wind stresses. Follow
all guidelines when using these for rooftop applications.
• Straps must be attached to the hood where they will not interfere with
the movement of the dampers.
Note:
For all rooftop installation, safety straps must be attached between the
hood(s) and the equipment support structure. Straps should be 3/16” (or
larger) vinyl-coated cables.
• Straps must be connected to both the hood and mounting structure
through using ¼” diameter (or larger) bolt.
• Theoutdoorunitandequipmentsupportshouldbermly
attached to the structure. If the equipment support does not at-
tach to the structure, refer to the support manufacturer’s
guidelines for proper size and construction.
Dependingonlocation,exposureandotherfactorsinuencingwind
access or blockage, additional support may be required such as
shown at right. Contact your distributor for assistance.