Mitsubishi Electronics H2iSD-1 Marine Battery User Manual


 
H2iSD-20
2010 Hyper-heating Y-SERIES SYSTEM DESIGN (Sept. 2010)
2010 H2i
®
Y-SERIES
SYSTEM DESIGN
2. M-NET CONTROL
2-4-3-10. LMAP
LMAP(01)
24VDC
(LONWORKS adapter)
PC
L
ON
W
ORKS
card
L
ON
W
ORKS
card
L
ON
W
ORKS
card
For other equipments (Lighting, security, elevator etc.)
LMAP can transmit for max.
50 indoor units in single-refrigerant-system or multi-refrigerant-system.
DipSW1-2
OFF
247
LONWORKS
PSU
000
AG-150A
Power supply unit
(PAC-SC51KUA)
identified by Neuron ID
LMAP(02)
DipSW1-2
ON
247
identified by Neuron ID
CN41
CN40
CN41
CN40
LMAP can transmit max. 50 indoor units;
If system controller (SC) is used, DipSW1-2 at LMAP and DipSW2-1 at Outdoor unit should set to "ON".
Change Jumper from CN41 to CN40 to activate power supply to LMAP itself for those LMAP connected without system
controller (SC).
Indoor unit
MA R/C MA R/C
(Main) (Sub)
MA R/C
SRU
Wireless R/C
*1
*1
01 02 03 42
TB15
TB5 TB5TB5 TB2
Transmission Booster
PAC-SF46EPA
TB5
TB15 TB15 TB3
TB15
Group 2Group 1
Group 40
TB7 TB7
TB3
TB3
5251
OC OS
CN41CN40CN41CN40
OFF
DipSW2-1
OFF
DipSW2-1
Indoor unit
ME R/C ME R/C ME R/C
01 02 03 30
TB5 TB5TB5 TB2
Transmission Booster
PAC-SF46EPA
TB5
ME R/C
101
102 130 180
TB3
Group 2
Group 1
Group 21
TB3
TB7TB7 TB7 TB7
TB7
TB3
5251
OC OS
TB3TB3
9291
OC OS
TB3
96
OC
CN41CN40CN41CN40
CN41
CN40CN41CN40 CN41CN40
ON
DipSW2-1
ON
DipSW2-1
ON
DipSW2-1
ON
DipSW2-1
ON
DipSW2-1
ME R/C ME R/C
Indoor unit
ME R/C
144 145 195
41 44 45
TB5 TB5 TB5
Group 31 Group 34 Group 35
ME R/C
141
PUHY-HP-TSJMU
PUHY-HP-TSJMU PUHY-HP-TSJMU PUHY-HP-TJMU
*1 For Wireless R/C and Signal receiver unit (SRU), channel 1, 2 and 3 are selectable and should be set to same channel.
ME R/CPZ-52SF
142 143
42
43
TB5
LOSSNAY
TB5
Group 32 Group 33