Emerson MAS 2600 Marine Instruments User Manual


 
Installation & User Manual
Ed 19UK June 2013
Page 4 of 28
0
100
200
300
400
500
600
700
17
20
23
26
29
32
Load resistance (ohm)
Power supply (V)
Max. load resistance
at various power supply
Technical Specifications
Transducer Ranges:
Gauge: 0-3.5 / 0-7 / 0-16 / 0-35 m H
2
O.
Absolute: 0-20.394 / 0-35.690 m H
2
O.
Programmable Measuring Ranges:
Each transducer range is programmable in 8
steps.
Accuracy:
± 0.25% F.S. at 20°C.
Stability:
Max. ± 0.1% / Year.
TEB (Total Error Band):
± 2.0% F.S. at -20 to +80°C.
EMC immunity influence < ±0.5%FS
Overload Capability:
Min. 4 x transducer range with no changes in
calibration.
6 x transducer range burst pressure.
Built-in Temperature Sensor Pt100:
Optional.
Power Supply:
The Power Supply can vary from 17-33
VDC. Permissible load resistance is shown
graphically below. Calculation formula:
R
loop max.
(Kohm) =
mA25
17V-U
Loop
Output Current:
4-20 mA DC, loop powered 2-wire system.
Current Limiting:
Max: 25 mA
Sensor Materials:
Housing: Titanium Grade 2
Diaphragm: Titanium Grade 4
Operating Temperature Ranges:
Transducer: -20 to +125°C
Standard cable: -20 to + 80°C
High temperature cable: -20 to +125°C
Amplifier: -40 to + 85°C
Protection Class:
Transducer: IP 68
Amplifier: IP 56
Intrinsic Safety:
Ex ia IIC T4 compliant.
Max. 75 m cable between transducer and
transmitter amplifier.
Transmitter dimensions
Amplifier box:
MARINE AUTOMATION DENMARK
Cint = 10 nF
2600 SERIES
4-20 mA
CERTIFICATE REF.:
Lint = 20 uH
x
EE
X
i
a
C
amb.: -40 to +85 °C
I 45 mA
S/N:
Umax = 33 V
T5
90-C.95948
2600
T
K=
<
TWO WIRE TRANSMITTER
55.0
110.0
75.0
45.0
98.0
PG11
cable gland
1/8" NPT
vent fitting
4 pcs. ø4.5
Use 4x20mm bolts and nuts
for suspension on a 4mm
thick surface
Transducer:
120.0
3.0
30.0
25.0
6-core vented cable, ø8.0
Front view