Mitsubishi Electronics FR-A740-0.4k to 500k Marine Battery User Manual


 
343
Communication operation and setting
4
PARAMETERS
Example) When reading the C3 (Pr. 902) and C6 (Pr. 904) settings from the inverter of station 0
To read/write C3 (Pr. 902) and C6 (Pr. 904) after inverter reset or parameter clear, execute from 1) again.
Parameter clear
All clear
Write HFC
All parameters return to the initial values.
Whether to clear communication parameters or not can be
selected according to data. ( : Clear, ×: Not clear)
Refer to page 466 for parameter clear, all clear, and communication
parameters.
When clear is executed for H9696 or H9966, communication-related
parameter settings also return to the initial values. When resuming
operation, set the parameters again.
Executing clear will clear the instruction code HEC, HF3, and HFF
settings.
In the password locked status (refer to page 310), only H9966 and H55AA
(all parameter clear) are valid.
*1 Turning OFF the power supply while clearing parameters with H5A5A or
H55AA also clears the communication parameter settings back to the initial
values.
4 digits
(A,C/D)
Parameters
Read
H00 to
H63
Refer to the instruction code (Refer to page 466) and write and/or read the
values as required.
When setting Pr. 100 and later, link parameter extended setting must be
set.
4 digits
(B.E/D)
Write
H80 to
HE3
4 digits
(A,C/D)
Link parameter
extended setting
Read H7F
Parameter description is changed according to the H00 to H09 setting.
For details of the setting, refer to the instruction code (Refer to page 466).
2 digits
(B.E'/D)
Write HFF
2 digits
(A',C/D)
Second
parameter
changing
(instruction code
HFF=1, 9)
Read H6C
When setting the calibration parameters
*1
H00:Frequency *2
H01: Parameter-set analog value
H02: Analog value input from terminal
*1 Refer to the list of calibration parameters on the next page for calibration
parameters.
*2 The gain frequency can also be written using Pr. 125 (instruction code H99) or
Pr. 126 (instruction code H9A).
2 digits
(B.E'/D)
Write HEC
2 digits
(A',C/D)
REMARKS
Set 65520 (HFFF0) as a parameter value "8888" and 65535 (HFFFF) as "9999".
For the instruction codes HFF, HEC and HF3, their values are held once written but cleared to zero when an inverter reset or all
clear is performed.
Computer Send Data Inverter Send Data Description
1)
ENQ 00 FF 0 01 82 ACK 00 Set "H01" in the extended link parameter.
2)
ENQ 00 EC 0 01 7E ACK 00 Set "H01" in second parameter changing.
3)
ENQ 00 5E 0 0F STX 00 0000 ETX 25 C3 (Pr. 902) is read. 0% is read.
4) ENQ 00 60 0 FB STX 00 0000 ETX 25 C6 (Pr. 904) is read. 0% is read.
Item
Read/
Write
Instruction
Code
Data Description
Number of
Data Digits
(format)
Refer to page 336 for data formats (A, A', B, B', C, D)
Clear Type Data Communication Pr.
Parameter clear
H9696
H5A5A ×
*1
All parameter clear
H9966
H55AA ×
*1