Mitsubishi Electronics FR-A740-0.4k to 500k Marine Battery User Manual


 
70
Operation panel (FR-DU07)
4.1.3 Changing the parameter setting value
4.1.4 Displaying the set frequency
Press the setting dial ( ) in the PU operation mode or in the External/PU combined operation mode 1 (Pr. 79 =
"3") to show the set frequency.
Changing example Change the Pr. 1 Maximum frequency .
Operation
1.
Screen at power-ON
The monitor display appears.
2.
Operation mode change
Press to choose the PU operation mode. [PU] indicator is lit.
3.
Parameter setting mode
Press to choose the parameter setting mode. (The parameter number read previously appears.)
4.
Selecting the parameter
Turn until (Pr. 1) appears. Press to read the present set value. " " (initial value) appears.
5.
Changing the setting value
Turn to change it to the set value " ". Press to set. " " and " " flicker alternately.
·By turning , you can read another parameter.
·Press to show the setting again.
·Press twice to show the next parameter.
·Press twice to return the monitor to frequency monitor.
are displayed ... Why?
appears. ......Write disable error
appears. ......Write error during operation
appears. ......Calibration error
appears. ......Mode designation error
For details refer to page 404.
REMARKS
The number of digits displayed on the operation panel (FR-DU07) is four.
If the values to be displayed have five digits or more including decimal places, the fifth or later numerals cannot be displayed nor
set.
(Example) When Pr. 1
When 60Hz is set, 60.00 is displayed.
When 120Hz is set, 120.0 is displayed and second decimal place is not displayed nor set.
POINT
When Pr.77 Parameter write selection = "0 (initial value)," the parameter setting change is only available while the
inverter is stopped under the PU operation mode.
To enable the parameter setting change while the inverter is running or under the operation mode other than PU
operation mode, change the Pr.77 setting
to