3. Press the Display button until the “Send” command appears on the
display.
4. Press the center or the right arrow button to manually force the
PowerLogic E4800 meter to report metering data using the Ethernet or
modem connection. This clears data from the PowerLogic E4800 meter
memory, and ensures the time is set correctly.
Pulse Inputs There are two pulse in terminal blocks in the PowerLogic meter, as shown in
Figure 10. Each terminal block has a negative terminal pin on the right and a
positive terminal pin on the left. The pulse inputs are compatible with both dry
form A contacts, and solid-state form A contacts. The inputs are not
polarity-sensitive to dry relay contacts. When the pulsing device provides
solid-state form A outputs, the negative terminal from the source device must
be connected to the negative terminal of the PowerLogic meter pulse in
terminal block.
Display Navigation The PowerLogic E4800 meter has three buttons to control the information
presented on the LCD. The display has a normal and a diagnostics mode.
The PowerLogic E4800 meter display starts in normal mode, and enters
diagnostics mode when the Display button is pressed and held for 5 seconds.
To adjust the contrast, hold down the Display button, and use the right and
left arrow buttons to increase and decrease the contrast respectively.