Schneider Electric E4800 Marine Instruments User Manual


 
PowerLogic
TM
E4800 Series 930-110-01
Introduction 02/2009
© 2009 Schneider Electric All Rights Reserved2
Table 1: PowerLogic E4800 meter specifications
Specification PowerLogic E4833 meter PowerLogic E4880 meter PowerLogic E4805 meter
Dimensions Height: 13.125 in. (33.5 cm)
Width: 12 in. (30.5 cm)
Depth: 2.125 in. (5.5 cm)
Height: 13.125 in. (33.5 cm)
Width: 12 in. (30.5 cm)
Depth: 2.125 in. (5.5 cm)
Height: 13.125 in. (33.5 cm)
Width: 17 in. (44 cm)
Depth: 2.125 in. (5.5 cm)
Weight 8.77 lb (3.98 kg) 8.77 lb (3.98 kg) 11.9 lb (5.4 kg)
Reference input voltage 208Y/120V, 3W+N+Protective Earth
208Y/120V, 2W+N+Protective Earth
120/240V, 2W+N+Protective Earth
208Y/120V, 3W+N+Protective Earth
208Y/120V, 2W+N+Protective Earth
120/240V, 2W+N+Protective Earth
208Y/120V, 3W+N+Protective Earth
208Y/120V, 2W+N+Protective Earth
120/240V, 2W+N+Protective Earth
Reference voltage
tolerance
+/-10% +/-10% +/-10%
Supply voltage and current North America: 120V 125 mA 60 Hz
International: 230-240V 63 mA 50/60
Hz
North America: 120V 125 mA 60 Hz
International: 230-240V 63 mA 50/60
Hz
North America: 120V 125 mA 60 Hz
International: 230-240V 63 mA 50/60
Hz
Current transformers
Measurement Category III
0.333 V secondary CT 200 A primary CT
80 mA secondary CT
5 A secondary CT
Measurement accuracy ANSI C12.20
.5 Accuracy Class
ANSI C12.20
.5 Accuracy Class
ANSI C12.20
.5 Accuracy Class
Pulse inputs 1 and 2 Dry form A and solid-state form A
compatible
Maximum frequency 10 Hz
Minimum pulse width 20 ms
Dry form A and solid-state form A
compatible
Maximum frequency 10 Hz
Minimum pulse width 20 ms
Dry form A and solid-state form A
compatible
Maximum frequency 10 Hz
Minimum pulse width 20 ms
Non-volatile memory
storage
120 days in 15-minute intervals 120 days in 15-minute intervals 120 days in 15-minute intervals
Onboard modem V.90, RJ11 V.90, RJ11 V.90, RJ11
Onboard Ethernet port 10/100 BaseTX 10/100 BaseTX 10/100 BaseTX
Serial port 115 kb/s 115 kb/s 115 kb/s
Fuse rating (F1) North America: 120V: F125 mA H
250V
International: N/A
North America: 120V: F125 mA H
250V
International: N/A
North America: 120V: F125 mA H
250V
International: N/A
Environmental
Operating temperature -40 to 70
o
C -40 to 70
o
C -40 to 70
o
C
Operating humidity 0 to 90% non-condensing 0 to 90% non-condensing 0 to 90% non-condensing
Usage environment Indoor or enclosed outdoor
environment
Indoor or enclosed outdoor
environment
Indoor or enclosed outdoor
environment
Maximum altitude 6562 ft (2000 m) 6562 ft (2000 m) 6562 ft (2000 m)
Pollution degree 2 2 2
Regulatory Compliance United States and Canada
Safety TUV and UL certified to
IEC/EA/UL/CSA 61010-1 2
nd
Edition
CSA-C22.2 No. 61010-1-04
TUV and UL certified to
IEC/EA/UL/CSA 61010-1 2
nd
Edition
CSA-C22.2 No. 61010-1-04
TUV and UL certified to
IEC/EA/UL/CSA 61010-1 2
nd
Edition
CSA-C22.2 No. 61010-1-04
Emissions (EMC) FCC Part 15 Class A, ICES-003
EN55022, IEC 6100-4-5
FCC Part 15 Class A, ICES-003
EN55022, IEC 6100-4-5
FCC Part 15 Class A, ICES-003
EN55022, IEC 6100-4-5
Surge power/telephone
lines