Schneider Electric PM810 Marine Instruments User Manual


 
© 2011 Schneider Electric. All Rights Reserved.
PowerLogic
TM
Series 800 Power Meter 63230-500-225A2
Appendix D—Advanced Power Quality Evaluations 3/2011
100
3906 1
Definition of Interruption (EN50160 only)
0 – 10% Nominal (default = 1)
3907 1
Allowable Range of Slow Voltage Variations (EN50160 only)
1 – 20% Nominal (default = 10)
3908 1 Reserved
3909 1 Reserved
3910 1
Bitmap of active evaluations
Bit 00 – Summary bit – at least one EN50160 evaluation is active
Bit 01 – Frequency
Bit 02 – Supply voltage variations
Bit 03 – Magnitude of rapid voltage changes
Bit 04 – Not used
Bit 05 – Supply voltage dips
Bit 06 – Short interruptions of the supply voltage
Bit 07 – Long interruptions of the supply voltage
Bit 08 – Temporary power frequency over-voltages
Bit 09 – Not used
Bit 10 – Supply voltage unbalance
Bit 11 – Harmonic voltage
Bit 12 – THD
Bit 13 – Not used
Bit 14 – Not used
Bit 15 – Not used
3911 1
Bitmap of evaluation status summary
Bit 00 – Summary bit – at least one EN50160 evaluation has failed.
Bit 01 – Frequency
Bit 02 – Supply voltage variations
Bit 03 – Magnitude of rapid voltage changes
Bit 04 – Not used
Bit 05 – Supply voltage dips
Bit 06 – Short interruptions of the supply voltage
Bit 07 – Long interruptions of the supply voltage
Bit 08 – Temporary power frequency over-voltages
Bit 09 – Not used
Bit 10 – Supply voltage unbalance
Bit 11 – Harmonic voltage
Bit 12 – THD
Bit 13 – Not used
Bit 14 – Not used
Bit 15 – Not used
3912 2 Count of 10-second intervals present year
3914 2 Count of 10-second intervals this week
3916 1 Count of 10-minute intervals this week
3917 1
Number of allowable rapid voltage changes per week
Default = -32768 = Pass/Fail evaluation disabled
3918 1
Number of allowable short interruptions per year
Default = -32768 = Pass/Fail evaluation disabled
3919 1
Number of allowable long interruptions per year
Default = -32768 = Pass/Fail evaluation disabled
3920 8
Number of allowable voltage dips per week for each range of Depth
Default = -32768 = Pass/Fail evaluation disabled
3930 8
Number of allowable over-voltages per week for each range of Magnitude
Default = -32768 = Pass/Fail evaluation disabled
Table D–11: PQ Advanced Evaluation System Configuration and Status Registers
Register Number Description