I/O (Input/Output) Setup
PASSW (Password) Setup
1. Perform steps 1 through 5 of the SETUP MODE
Access procedure on page 11.
2. Press
###: until I/O is visible.
3. Press I/O.
4. Press D OUT for digital output or D IN for digital
input, or press A OUT for analog output or A IN
for analog input. Use the ###: button to scroll
through these selections.
NOTE: Analog inputs and outputs are available
only with the PM8222 option module.
5. Press EDIT.
6. Select the I/O mode based on the I/O type and
the user selected mode: NORM., LATCH,
TIMED, PULSE, or END OF.
7. Depending on the mode selected, the power
meter will prompt you to enter the pulse weight,
timer, and control.
8. Press OK.
9. Select EXT. (externally controlled via
communications) or ALARM (controlled by an
alarm).
10. Press
1; to return to the SETUP MODE screen.
11. At the SETUP MODE screen, continue
programming additional setup features or
press
1; until you are asked to save changes.
12. Press YES to save the changes.

+9
 /+
05,3%
4)-%2
%84

./2-
PLSD110221
1. Perform steps 1 through 5 of the SETUP MODE
Access procedure on page 11.
2. Press
###: until PASSW (password) is visible.
3. Press PASSW.
4. Enter the SETUP password.
5. Press OK.
6. Enter the DIAG (diagnostics) password.
7. Press OK.
8. Enter the ENERG (energy reset) password.
9. Press OK.
10. Enter the MN/MX (minimum/maximum reset)
password.
11. Press OK.
12. At the SETUP MODE screen, continue
programming additional setup features or
press
1; until you are asked to save changes.
13. Press YES to save the changes.
