Schneider Electric PM810 Marine Instruments User Manual


 
© 2011 Schneider Electric. All Rights Reserved.
63230-500-225A2 PowerLogic
TM
Series 800 Power Meter
3/2011 Chapter 7—Logging
63
Configure the Billing Log Logging Interval
The billing log can be configured to update every 10 to 1,440 minutes. The default logging
interval is 60 minutes. To set the logging interval you can use PowerLogic software, or you
can use the power meter to write the logging interval to register 3085 (see “Read and
Write Registers” on page 26).
Table 7–6: Billing Log Register List
Description
Number of
Registers
Data Type Register Number
Start Date/Time 3 D/T Current D/T
Real Energy In 4 MOD10L4 1700
Reactive Energy In 4 MOD10L4 1704
Real Energy Out 4 MOD10L4 1708
Reactive Energy Out 4 MOD10L4 1712
Apparent Energy Total 4 MOD10L4 1724
Total PF 1 INT16 1163
3P Real Power Demand 1 INT16 2151
3P Apparent Power Demand 1 INT16 2181
Refer to Appendix A for more information about data types.