Xantrex Technology HI400 SONAR User Manual


 
Installing the HI400
17
Permanently connecting (hardwiring) the AC output
To hardwire the AC output connections:
1. Remove the AC hardwire compartment cover. Three
wires are located inside the wiring compartment as
follows:
Black – the AC output line conductor
White – the AC output neutral conductor
Red – the ignition lockout conductor (page 18)
2. Run No. 14 AWG 2-conductor-plus-ground cable
through the cable clamp and into the AC wiring
compartment.
3. Strip about 2 inches off the jacket of the AC cable.
4. Strip approximately ½ inch off the insulation of the black
and white wires from the AC cable (if using the twist-on
wire connectors provided). If you are providing your own
connectors, follow the manufacturer’s recommendations
regarding strip length and use of the connectors.
WARNING: Fire, shock, and energy
hazards
Make sure wiring is disconnected from all electrical
sources before handling. All wiring must be done in
accordance with local and national electrical wiring
codes. Do not connect the output leads of the inverter to
any incoming AC source.
WARNING: Shock hazard
Do not connect the ignition lockout wire (red) to AC
circuits. See instructions for connecting on page 18.