A SERVICE OF

logo

Publication 20D-UM002C-EN-P - November 2003
Communicating with Devices on a DH-485 Link 10-7
Single Cable Connection
Connections Using Belden 3106 Cable
The table and schematic diagram below shows wire/terminal connections for
Belden 3106A cable.
For this Wire/Pair Connect this Wire To this Terminal
white/orange orange with white stripe 5 - Data A)
white with orange stripe 4 - (Data B)
blue blue 3 - (Common)
shield/drain non-jacketed 2 - Shield
Belden 3106A or 9842 Cable
(3106A Shown)
Shrink Tubing
(Recommended)
White Wire
with Orange Stripe
(WH/OR)
Orange Wire
with White Stripe
(OR/WH)
Blue Wire
(BU)
Drain Wire
(Shield)
6 Termination
5 Data A
4 Data B
3 Common
2 Shield
1 Chassis Ground
Termination
Data A
Data B
Common
Shield
Chassis Ground
WH/OR
OR/WH
BU
6
5
4
3
2
1