Publication 20D-UM002C-EN-P - November 2003
Placing and Configuring the Drive 3-23
Accessing Drive Data
Drive data is displayed as structures of multiple tags. The names and data
structures are based on the selected communication format. The programming
software automatically creates the necessary structures and tags when you
configure the drive module. Each tag name follows this format:
ModuleName:Type.MemberName.SubMemberName.Bit
where:
Refer to Communication Formats on page 3-6 for sample tag names.
Monitoring Drive Data
The DriveLogix controller offers different levels at which you can monitor the
drive module. You can:
configure the drive module so that the controller faults if the drive loses
its connection to the controller.
use the programming software to display fault data
program logic to monitor fault data so you can take appropriate action
This address
variable:
Is:
ModuleName Identifies the module name entered during the drive module
configuration
Type Type of data
I = input
O = output
MemberName Specific data from the drive; depends on the selected
communication format.
For tags associated with pre-defined data links, this name will
be the same as the corresponding parameter name in the drive.
SubMemberName Specific data related to a MemberName
Bit (optional) Specific bit of a DINT data value