Switchover with gap:
The switchover from INV to SBS is carried out without interruption if
the INV and SBS circuit are synchronous. If the INV and SBS circuit
are not synchronous, the SBS does not block in this operating mode.
If the INV is switched off due to asynchronism or if it fails, the load is
supplied by the SBS after a load voltage gap of 140 ms.
i
NOTE:
If the operating mode "Switchover with gap" is selected, the
connected loads must be able to withstand a gap of 140 ms and a
phase shift that might follow.