AEG 8000012364 BAL Marine Battery User Manual


 
"UniVert 2" inverter
Page 38 of 42 8000012364 BAL, en
Type
E-number
G110 E230/10,9/2rfg-CFp2,5
3000000263
Rated output capacity 2.5 kVA
with power factor 0.8
Power factor range 0 inductive to 0 capacitive
Rated output voltage
230 V ±0.5 static, ±3% dynamic at 100% load change
Output frequency
50 Hz ±0.05%
THD factor < 3%
Rated output current 10.9 A
DC rated input voltage 110 V -15% ... +20%
DC rated current 20.4 A at 110 V
Efficiency >88%
DC input current ripple < 50% of DC rated current
Monitoring systems
DC undervoltage, switch-off Fault < 85% of 110 V (93.5 V), without delay
Acknowledgement > 103% of 110 V (113.3 V), 15 s delay
DC overvoltage, switch-off Fault > 128% of 110 V (140.8 V), without delay
Acknowledgement < 125% of 110 V (137 V), 15 s delay
AC undervoltage, switch-off Fault < 90% rated (207 V), 2.5 s delay
Acknowledgement by ON/OFF switch
Overtemperature, switch-off
Fault > 80 °C, acknowledgement < 70 °C, approx. 5 s delay