"UniVert 2" inverter
Page 33 of 42 8000012364 BAL, en
Mechanical stability
and vibration resistance.................To VDE 0160 Version 5.88
Item 7.2.2
Surface painted with ......................RAL 7032 (front panel)
Dimensions (w x h x d) ..................483 x 174 x 460 mm
(19" x 4 height modules)
(type 1.5 and 3.3 kVA)
483 x 174 x 400 mm
(19" x 4 height modules)
(type 2.5 kVA)
Weight ...........................................Approx. 46.5 kg (type 3.3 kVA)
Approx. 39 kg (type 2.5 kVA)
Approx. 33.1 kg (type 1.5 kVA)
Noise generation ...........................< 50 dB(A)
Connections
X1 DC input: ..................................Screw terminal 10 ... 25 mm²
(type 1.5 and 3.3 kVA)
Screw terminal 0.5 ... 10 mm²
(type 2.5 kVA)
X2 AC output: ................................Screw terminal 0.5 ... 10 mm²
X3 remote signals:.........................Screw terminal 0.2 ... 2.5 mm
2
PE conductor: ................................M4 thread
CAN bus interface X6 ....................10-pin socket connector with
insulation displacement
technology
in acc. with DIN 41651
CAN bus interface X7 ....................16-pin socket connector with
insulation displacement
technology
in acc. with DIN 41651
8.2 General Data SBS
Required AC fuse ..........................Max. gL 125 A
Manufacturing and type test ..........In acc. with DIN 60146 Part 1-1
Emitted interference in acc. with EN 50081-1
- Conducted interference ..............In acc. with EN 55022 Class "B"
- Emission......................................In acc. with EN 55022 Class "B"
Noise immunity in acc. with EN 50082-2
- Housing .......................................ESD test to EN 61000-4-2,
6 kV contact
HF field to EN 61000-4-3,
10 V/m (30 MHz – 1 GHz)