1-3 PRODUCT OVERVIEW
The OPTIMizer Hand Held Programmer is required for all
OPTIM Trip Unit Systems. It plugs into the front of
OPTIM 550, 750 or 1050 Trip Units and is powered by a
standard nine volt battery (Figure 1-1) or auxiliary power
module. The OPTIMizer accesses, displays, and config-
ures information from OPTIM Trip Units. The OPTIMizer
Hand Held Programmer provides a broad range of pro-
gramming possibilities available with the OPTIM Trip Unit
System and the range of compatible circuit breakers.
1-4 FEATURES AND FUNCTIONS
An OPTIMizer must be used to configure the trip unit for
communications on the INCOM Network. This requires
an operator, during initial start-up, to:
Assign Unique Device Addresses
Select Baud Rates
In addition, the OPTIMizer can be used to:
Configure OPTIM Trip Unit
- Select frequency (50/60 Hz)
- Set security passwords
- Change time-current setpoints
- Select protection options
- Select High Load Alarm level
Display Information
- Breaker description
- Time-current setpoints
- Metered values
- Trip event information
Test OPTIM Trip Unit Performance
- Phase and ground
- Trip or no trip
Communicate over INCOM
• Copy Trip Unit Settings
- To download to any OPTIM breaker of any type
Figure 1-1 Hand Held Programmer in Use with Series C
R-Frame Circuit Breaker