GE EPM 5300 Marine Instruments User Manual


 
4–28 EPM 5300 SERIES ADVANCED POWER METERS – INSTRUCTION MANUAL
NETWORK OF INSTRUMENTS AND LONG DISTANCE COMMUNICATION CHAPTER 4: COMMUNICATION INSTALLATION
Necessary to communicate with remote modem connected to EPM 5300P.
Tell modem to write the new settings to activate profile:
Places new settings into nonvolatile memory; settings take effect after the modem
powers up.
Debugging Communication Problems
If you experience NO communication, check these conditions:
Is the Baud Rate set correctly (see Part II: Programming Section)?
Is the Meter Address set correctly (see Part II: Programming Section)?
Is the correct protocol set? Modbus, DNP 3.0?
Set the meter for the appropriate protocol for the internal software.