11–84 EPM 5300 SERIES ADVANCED POWER METERS – INSTRUCTION MANUAL
CALIBRATION REQUIREMENTS CHAPTER 11: PROGRAMMING GROUP 2 - METER CALIBRATION
11.1 Calibration Requirements
Calibration on the EPM 5300P requires precise inputs of 120 Volts, 5 Amps, and 2.5 Amps.
The EPM 5300P -G model requires precise inputs of 300 Volts, 5 Amps, and 2.5 Amps. If this
equipment is unavailable, contact us for assistance.
Note
The voltage and current scales are calibrated with the maximum range value 2000 for
current, 14.40 for voltage, 300 for option G. The calibration value can be identical to the
full scale value in GROUP 1, for better accuracy than the specification. However, if a full
scale is ever changed to a higher value than the calibrated value, the value may be less
accurate.
Table 11–1: Group 2 Programming Format
Group and Function Number Function
20. High End Calibration—Volts AN, BN, CN
21. High End Calibration—Amps A, B, C
22. Low End Calibration—Amps A, B, C
2E. Exit Programming Group 2
Table 11–2: Calibration Source, Full Scale and Value Settings for Calibration
Voltage Range Input Source Group 2 Value
69.3/120V 75V 1440
120/208V 120V L-N 1440
277/480V 300V 0300
5A CT High End 5A 2000
2.5A Low End 2.5A 1000