GE EPM 5350 Marine Instruments User Manual


 
CHAPTER 16: ETHERNET OPTION ETHERNET OPTION SETUP
EPM 5300 SERIES ADVANCED POWER METERS – INSTRUCTION MANUAL 16–121
Use a Telnet connection to configure the unit over the network. The Ethernet Interface’s
configuration is stored in nonvolatile memory (NVRam) and is retained without power. The
configuration can be changed at any time. The Ethernet Interface performs a reset after
the configuration has been changed and stored.
As mentioned above, to configure the Ethernet Interface over the network, establish a
Telnet connection to port 9999. From the Windows Start menu, click Run and type the
following command, where x.x.x.x is the IP address and 9999 is the Ethernet Interface’s
fixed network configuration port number.
telnet x.x.x.x 9999
Note
Be sure to include a space between the IP address and 9999.
16.2.5 Configuration Parameters
After entering Setup Mode (confirm by pressing Enter), you an configure the parameters by
entering one of the numbers on the Change Setup Menu, or you can confirm default values
by pressing Enter. Be sure to store new configurations when you are finished. The
Ethernet Interface will then perform a power reset.
Serial Number 5415404 MAC Address 00:20:4A:54:3C:2C
Software Version V01.2 (000719)
Press Enter to go into Setup Mode
1. Network/IP Settings:
Ethernet Interface Autodetect
IP Address - 0.0.0.0/DHCP (Customer Configurable)
Default Gateway --- not set --- (Customer Configurable)
Netmask --- not set --- (Customer Configurable)
2. Serial & Mode Settings:
Protocol Modbus/RTU, Slave(s) attached (FIXED)
Serial Interface 9600,8,N,1,RS232,DB25 (must match meter)
(FIXED)
3. Modem Control Settings:
DCD Output Fixed High/Active
CTS Output Fixed High Active
4. Advanced Modbus Protocol Settings:
Slave Addr/Unit Id Source Modbus/TCP header (FIXED)
Modbus Serial Broadcasts Disabled
Character, Message Timeout 00010 ms, 00500 ms
D) default settings, S) save, Q) quit without save;
select command or parameter set (1..4) to change: I