GE EPM 5350 Marine Instruments User Manual


 
CHAPTER 9: PROGRAMMING GROUP 0 - GLOBAL METER SETUP GROUP 0, FUNCTION 3—PROGRAMMING PROCEDURE
EPM 5300 SERIES ADVANCED POWER METERS – INSTRUCTION MANUAL 9–61
9.5 Group 0, Function 3—Programming Procedure
To change the System Configuration Switch Settings:
Note
Press MAX/MIN/LIMITS, at any time, to cancel before storing the last digit or switch.
Step 1:
a. Enter Group Level of Programming Mode (see Chp. 8).
b. Press MAX/MIN/LIMITS until 0. appears in upper
display.
c. Press AMPS to activate the Group.
Step 2:
a. Press MAX/MIN/LIMITS until Function 03.0 appears in
upper display.
Lower display indicates current PACK 0 Switch
Settings.
Step 3:
a. Press VOLTS until desired PACK appears.
b. Press AMPS to begin Data Entry Sequence.
The previous Switch settings shift to middle display
and four dashes appear in lower display.
c. Press VOLTS to toggle the segments up or down for
desired setting.
d. Press AMPS to store each setting.
Repeat procedure until new Switch Setting is entered.
The middle display blanks and new Switch Settings are
indicated on lower display.
(This example shows enabling of Open Delta Installation
switch).
See Chapter 14 to Exit.
MAX/MIN
LIMITS
KVAR
PF
KW
KVA
FREQ
KWHKVAH
AC VOLTS
AC AMPS
POWER
NC
B
A
MAX
MIN
A
N
B
N
C
N
A
B
B
C
C
A
LM2
LM1
NEXT
PHASE
VOLTS
AMPS
POWER
MAX/MIN
LIMITS
KVAR
PF
KW
KVA
FREQ
KWHKVAH
AC VOLTS
AC AMPS
POWER
NCBA
MAX
MIN
A
N
B
N
C
N
A
B
B
C
C
A
LM2
LM1
NEXT
PHASE
VOLTS
AMPS
POWER
MAX/MIN
LIMITS
KVAR
PF
KW
KVA
FREQ
KWHKVAH
AC VOLTS
AC AMPS
POWER
NC
B
A
MAX
MIN
A
N
B
N
C
N
A
B
B
C
C
A
LM2
LM1
NEXT
PHASE
VOLTS
AMPS
POWER
MAX/MIN
LIMITS
KVAR
PF
KW
KVA
FREQ
KWH
KVAH
AC VOLTS
AC AMPS
POWER
NC
B
A
MAX
MIN
A
N
B
N
C
N
A
B
B
C
C
A
LM2
LM1
NEXT
PHASE
VOLTS
AMPS
POWER