9–66 EPM 5300 SERIES ADVANCED POWER METERS – INSTRUCTION MANUAL
GROUP 0, FUNCTIONS 4–5—TIME DELAY FOR RELAYS 1 & 2 (OPTION – NL)CHAPTER 9: PROGRAMMING GROUP 0 - GLOBAL METER SETUP
Step 1:
a. Enter Group Level of Programming Mode
(see Chp. 8).
b. Press MAX/MIN/LIMITS until 0. appears in upper
display.
c. Press AMPS to activate the Group.
Step 2:
To program Relay 1:
a. Press MAX/MIN/LIMITS until Function 04.P appears
in upper display.
To program Relay 2 and 3:
a. Press MAX/MIN/LIMITS until Function 05.P appears.
b. Press VOLTS once to display 04.0 (On to Off delay time).
c. Press VOLTS twice to display 04.1 (Off to On delay
time).
Lower display indicates current Time Delays.
MAX/MIN
LIMITS
KVAR
PF
KW
KVA
FREQ
KWHKVAH
AC VOLTS
AC AMPS
POWER
NC
B
A
MAX
MIN
A
N
B
N
C
N
A
B
B
C
C
A
LM2
LM1
NEXT
PHASE
VOLTS
AMPS
POWER
MAX/MIN
LIMITS
KVAR
PF
KW
KVA
FREQ
KWHKVAH
AC VOLTS
AC AMPS
POWER
NC
B
A
MAX
MIN
A
N
B
N
C
N
A
B
B
C
C
A
LM2
LM1
NEXT
PHASE
VOLTS
AMPS
POWER
Step 3:
a. Press AMPS to begin Data Entry Sequence.
The previous value shifts to middle display and four
dashes appear in lower display.
b. Press VOLTS until number appears.
c. Press AMPS to store each number.
Repeat this procedure until new Time Delay is entered.
When complete, middle display blanks and lower
display indicate the new Time Delay.
See Chapter 14 to Exit.
MAX/MIN
LIMITS
KVAR
PF
KW
KVA
FREQ
KWHKVAH
AC VOLTS
AC AMPS
POWER
NC
B
A
MAX
MIN
A
N
B
N
C
N
A
B
B
C
C
A
LM2
LM1
NEXT
PHASE
VOLTS
AMPS
POWER
MAX/MIN
LIMITS
KVAR
PF
KW
KVA
FREQ
KWHKVAH
AC VOLTS
AC AMPS
POWER
NCBA
MAX
MIN
A
N
B
N
C
N
A
B
B
C
C
A
LM2
LM1
NEXT
PHASE
VOLTS
AMPS
POWER