Mitsubishi Electronics FR-F740P Marine Battery User Manual


 
168
Operation selection at power failure and
instantaneous power failure
4.13.3 Power failure signal (Y67 signal)
When output is shutoff due to a power failure or undervoltage, the Y67 signal turns ON regardless of the automatic
restart after instantaneous power failure function setting.
Y67 signal turns OFF at power failure recovery or undervoltage recovery.
To use Y67 signal, set "67 (positive logic) or 167 (negative logic)" in any of Pr. 190 to Pr. 192 (Output terminal function
selection) to assign the function.
CAUTION
Changing the terminal assignment using Pr.190 to Pr.196 (Output terminal function selection) may affect the other functions. Set
parameters after confirming the function of each terminal.
Parameters referred to
Pr. 190 to Pr. 196 (output terminal function selection) Refer to page 140
Recovery after power failure
Y67
Time
OFF
Power supply
Output frequency
ONON
ON OFFOFF
Converter voltage recovery after E.UVT
Y67
Time
ON
Power supply
Output frequency
ON
OFFOFF
E.UVT occurrence
Converter voltage recovery