Mitsubishi Electronics FR-F740P Marine Battery User Manual


 
1/2 BCN-C22005-632
FR-F700P Series
Instruction Manual Supplement
For the FR-F700P series manufactured in July 2012 or later, the following specifications are added or
modified. Check the serial number printed on the rating plate or on package of the inverter. (For how to
find the SERIAL number, refer to the Instruction Manual.)
1 Voltage reduction selection during stall prevention operation (Pr.154)
(1) To further prevent a trip (Pr. 154)
<V/F><S MFVC>
When Pr. 154 is set to "0, 10", the output voltage reduces during stall prevention operation. By making this
setting to reduce the output voltage, an overcurrent trip can be less likely to occur. Use this function where a
torque decrease will not pose a problem.
Set Pr.154 = "10, 11" when the overvoltage protective function (E.OV) activates during stall prevention
operation in an application with large load inertia. Note that turning OFF the start signal (STF/STR) or
varying the frequency signal during stall prevention operation may delay the acceleration/deceleration
start.
(2) Causes and corrective actions
The setting values "10 and 11" are added for Pr.154 Voltage reduction selection during stall prevention operation.
Parameter
Number
Name
Initial
Value
Setting
Range
Description
154
Voltage reduction selection
during stall prevention
operation
1
0
With voltage
reduction
You can select whether to use
output voltage reduction during
stall prevention operation or not.
1
Without voltage
reduction
10
With voltage
reduction
Use these settings when the
overvoltage protective function
(E.OV) activates during stall
prevention operation in an
application with large load inertia.
11
Without voltage
reduction
Operation Panel
Indication
E.OV1
FR-PU04
FR-PU07
OV During Acc
Name
Regenerative overvoltage trip during acceleration
Description
If regenerative energy causes the inverter's internal main circuit DC voltage to reach or exceed the
specified value, the protective circuit is activated to stop the inverter output. The circuit may also be
activated by a surge voltage produced in the power supply system.
Check point
· Check for too slow acceleration. (e.g. during descending acceleration with lifting load)
· Check if Pr.22 Stall prevention operation level is set too low like the no-load current.
Check if the stall prevention operation is frequently activated in an application with a large
load inertia.
Corrective action
· Decrease the acceleration time.
· Use the regeneration avoidance function (Pr. 882 to Pr. 886). ( Refer to Chapter 4 of the Instruction
Manual (Applied).)
· Set a value larger than the no load current in Pr. 22 Stall prevention operation level.
Set Pr.154 Voltage reduction selection during stall prevention operation = "10 or 11". ( Refer to
Chapter 4 of the Instruction Manual (Applied).)
V/FV/FV/F
S
MFVC
S
MFVC
S
MFVC
V/FV/FV/F
S
MFVC
S
MFVC
S
MFVC