Useful functions
4
PARAMETERS
(2) Automatic parameter setting using the operation panel (parameter setting mode)
Operation example
The communication setting parameters for the GOT connection with a PU connector are
automatically set.
Pr.999 setting Description Operation in the parameter setting mode
10 GOT initial setting (PU connector)
(AUTO) (GOT) Write "1"
20 50Hz rated frequency
(AUTO) (F50) Write "1"
31
Acceleration/deceleration time
(0.01s increment)
(AUTO) (T0.01) Write "1"
are displayed alternately ... Why?
The inverter is not in the PU operation mode.
1.Press .
is lit and the monitor (4-digit LED) displays "0." (When Pr.79="0 (initial setting)")
2. Carry out operation from step 3 again.
PU indicator is lit.
2.
Press to choose the PU operation mode.
The parameter
number read
previously appears.
Operation
Display
3.
Press to choose the
parameter setting mode.
4.
Turn until (AUTO)
appears.
5.
Press to enter the automatic
parameter setting mode.
7.
Press to read the present set value.
" " appears.
6.
Turn until (GOT) appears.
1.
Screen at power-ON
The monitor display appears.
Flicker Parameter setting complete!!
9.
Press to set.
Turn to read another parameter.
Press twice to show the next parameter.
Press to show the setting again.
8.
Turn to change it to the set value " ".