Schneider Electric EM3555 Marine Instruments User Manual


 
13
© 2011 Schneider Electric All Rights Reserved.
ZL0093-0A
11/2011
EM3555
Quick Setup Instructions
QUICK SETUP INSTRUCTIONS
These instructions assume the meter is set to factory defaults. If it has been
previously congured, all optional values should be checked.
1. Press the
+
or
button repeatedly until SETUP screen appears.
2. Press to the PASWD screen.
3. Press through the digits. Press
+
or
to select the password (the default
is 00000). Exit the screen to the right.
4. Press
+
or
to select the parameter to configure.
5. The first Setup screen is S COM (set RS-485 communications).
a. Press to the ADDR screen and through the address digits. Press
+
or
to select the Modbus address.
b. Press to the BAUD screen. Press
+
or
to select the baud rate.
c. Press to the PAR screen. Press
+
or
to select the parity.
d. Press back to the S COM screen.
6. Press
to the S CT (Set Current Transducer) screen.
a. Press to the CT V screen. Press
+
or
to select the voltage mode
Current Transducer output voltage (default is 0.33).
b. Press to the CT SZ screen and through the digits. Press
+
or
to
select the CT size in amps.
c. Press back to the S CT screen.
7. Press
to the S SYS (Set System) screen.
a. Press to the SYSTM screen. Press
+
or
to select the System Type
(see wiring diagrams).
b. Press back to the S SYS screen.
8. (Optional) Press
to the S PT (Set Potential Transformer) screen. If PTs
are not used, then skip this step.
a. to the RATIO screen and through the digits. Use the
+
or
buttons
to select the Potential Transformer step down ratio.
b. back to the S PT screen.
9.
to the S V (Set System Voltage) screen.
a. to the VLL (or VLN if system is 1L-1n) screen and through the digits.
Use the
+
or
buttons to select the Line to Line System Voltage.
b. back to the S V screen.
10. Use the to exit the setup screen and then SETUP.
11. Check that the wrench is not displayed on the LCD.
a. If the wrench is displayed, press
+
or
to nd the ALERT screen.
b. Press through the screens to see which alert is on.
For full setup instructions, see the conguration instructions on the following