Schneider Electric EM3555 Marine Instruments User Manual


 
23
© 2011 Schneider Electric All Rights Reserved.
ZL0093-0A
11/2011
EM3555
Standard Modbus Default Settings
STANDARD MODBUS DEFAULT SETTINGS
Table 7 Modbus Default Settings
Setting Value Modbus
Register
Setup Password 00000
Reset Password 00000
System Type 40 (3 + N) Wye 130
CT Primary Ratio (if CTs
are not included)
100 A 131
CT Secondary Ratio 0.33 V 132
PT Ratio 1:1 (none) 133
System Voltage 600 V L-L 134
Max. Theoretical Power
(Analog Output: full scale
(20mA or 5V))
104 kW 135
Display Mode 1 (IEEE) 137
Phase Loss 10% of System Voltage (60V), 25%
Phase to Phase Imbalance
142, 143
Pulse Energy 1 (kWh/pulse) 144
Demand: number of
sub-intervals per interval
1 (block mode) 149
Demand: sub-interval
length
900 sec (15 min) 150
Modbus Address 001
Modbus Baud Rate 19200 baud
Modbus Parity Even
Log Read Page 0 158
Logging Conguration
Register
0 159
Log Register Pointer 1 1 (Real Energy MSR) 169
Log Register Pointer 2 2 (Real Energy LSR) 170
Log Register Pointer 3 29 (Reactive Energy MSR) 171
Log Register Pointer 4 30 (Reactive Energy LSR) 172
Log Register Pointer 5 37 (Real Demand) 173
Log Register Pointer 6 38 (Reactive Demand) 174
Log Register Pointer 7 39 (Apparent Demand) 175
Log Register Pointer 8 155 (Month/Day) 176
Log Register Pointer 9 156 (Year/Hour) 177
Log Register Pointer 10 157 (Minutes/Seconds) 178