Schneider Electric EM3555 Marine Instruments User Manual


 
33
© 2011 Schneider Electric All Rights Reserved.
ZL0093-0A
11/2011
EM3555
Modbus Point Map
REGISTER
R/W
NV
Format
Units
Scale
Range
Description
161 R NV UInt 0-32767
Log Buffer Wrap / Missed Log Counter. In continuous mode, this counter increments each time the
internal circular log buffer wraps and overwrites old data. The total number of logged entries since the
last log reset is: (Register 161 x 5760) + Register 163. In single shot mode this counter is the number of
log entries lost due to the buffer being full. The counter is cleared on logging reset.
162 R NV UInt 0-32767
Max Number of Logging Days. Based on the Sub-Interval Length and the depth of the log buffer, this
register shows the maximum number of days that data will be logged following a reset until the Buffer is
full (Single Shot Mode) or overwrites old data (Continuous).
163 R NV UInt 0-32767
Number of Logged Entries since the log buffer wrapped or was reset. In single shot mode, this is the
total number of valid entries in the buffer. Any entries beyond this will read back as QNAN (0x8000).
164
R NV ULong kWh E
0-0xFFFF
Real Energy Consumption
(MSR)
Real Energy (Register 001/002) starting value. Corresponds to when
logging is started, reset, or rolls.
165 0-0xFFFF
Real Energy Consumption
(LSR)
166 R NV UInt
Month /
Day
See Bytes
Most Signicant Byte (MSB)
Least Signicant Byte
(LSB)
Date & Time of the newest entry in the log. After a
power cycle, resets to:
Day 01 Month 01
Hour 00 Year (20) 00
Day 1-31 (0x01-0x1F)
Month 1-12
(0x01-0x0C)
167 R NV UInt
Year /
Hour
See Bytes Hour 0-23 (0x00-0x17)
Year 0-199
(0x00-0xC7)
168 R NV UInt
Minutes
/
Seconds
See Bytes Seconds 0-59 (0x00-0x3B)
Minutes 0-59
(0x00-0x3B)
169 R/W NV UInt
1-42,
146,
155-157,
257-336
Log Register 1 –
Default is 3 (Import Real
Energy MSR)
Log Register Selection – Write the number of the 16 bit register to be
logged. To log a 32 bit value (such as accumulators and oating point
values) two log registers must be used, one each for the most and least
signicant register (MSR & LSR).
170 R/W NV UInt
Log Register 2 –
Default is 4 (Import Real
Energy LSR)
171 R/W NV UInt
Log Register 3 –
Default is 5 (Export Real
Energy MSR)
172 R/W NV UInt
Log Register 4 –
Default is 6 (Export Real
Energy LSR)
173 R/W NV UInt
Log Register 5 –
Default is 29 (Real Demand)
174 R/W NV UInt
Log Register 6 –
Default is 30 (Reactive
Demand)
175 R/W NV UInt
Log Register 7 –
Default is 31 (Apparent
Demand)
176 R/W NV UInt
Log Register 8 –
Default is 155 (Month/Day)
177 R/W NV UInt
Log Register 9 –
Default is 156 (Year/Hour)
178 R/W NV UInt
Log Register 10 –
Default is 157 (Minutes/
Seconds)