Schneider Electric EM3555 Marine Instruments User Manual


 
27
© 2011 Schneider Electric All Rights Reserved.
ZL0093-0A
11/2011
EM3555
Modbus Point Map
REGISTER
R/W
NV
Format
Units
Scale
Range
Description
032 R NV SInt kW W
-32767 to
+32767
Total Real Power Max. Demand
Import
Reset via register
129
033 R NV SInt kVAR W
-32767 to
+32767
Total Reactive Power Max. Demand
034 R NV SInt kVA W
-32767 to
+32767
Total Apparent Power Max. Demand
035 R NV SInt kW W
-32767 to
+32767
Total Real Power Max. Demand
Export036 R NV SInt kVAR W
-32767 to
+32767
Total Reactive Power Max. Demand
037 R NV SInt kVA W
-32767 to
+32767
Total Apparent Power Max. Demand
038 R UInt Reserved (returns 0x8000 - QNAN)
039
R NV ULong
0 to
0xFFFFFFFF
Pulse Counter 1
(Import Real Energy)
MSR
Contact Closure Counters. Valid for both pulse
inputs and outputs. EM3555 counts are shown in
parentheses. See register 144 - Energy Per Pulse
for the Wh per pulse count.
040 LSR
041
R NV ULong
0 to
0xFFFFFFFF
Pulse Counter 2
(Export Real Energy)
MSR
042 LSR
043
R NV ULong kWh E
0 to
0xFFFFFFFF
Accumulated Real Energy,
Phase A
MSR
Import
Accumulated Real
Energy (Ph), per
phase
044 LSR
045
R NV ULong kWh E
0 to
0xFFFFFFFF
Accumulated Real Energy,
Phase B
MSR
046 LSR
047
R NV ULong kWh E
0 to
0xFFFFFFFF
Accumulated Real Energy,
Phase C
MSR
048 LSR
049
R NV ULong kWh E
0 to
0xFFFFFFFF
Accumulated Real Energy,
Phase A
MSR
Export
050 LSR
051
R NV ULong kWh E
0 to
0xFFFFFFFF
Accumulated Real Energy,
Phase B
MSR
052 LSR
053
R NV ULong kWh E
0 to
0xFFFFFFFF
Accumulated Real Energy,
Phase C
MSR
054
LSR