EM3555
Specifications
Type Description
Environmental Conditions
Operating Temperature -30° to 70°C (-22° to 158°F)
Storage Temperature -40° to 85°C (-40° to 185°F)
Humidity Range <95% RH (non-condensing)
Altitude of Operation 3 km max.
Metering Category
US and Canada CAT III; for distribution systems up to 347 V
L-N
/600 VAC
L-L
CE CAT III; for distribution systems up to 300 V
L-N
/480 VAC
L-L
Dielectric Withstand Per UL 508, EN61010
Conducted and Radiated
Emissions
FCC part 15 Class B, EN55011/EN61000 Class B;
(residential and light industrial)
Conducted and Radiated
Immunity
EN61000 Class A (heavy industrial)
Safety
US and Canada (cULus) UL508 (open type device)/CSA 22.2 No. 14-05
Europe (CE) EN61010-1:2001
* External DC current limiting is required, see fuse recommendations.
For use in a Pollution Degree 2 or better environment only. A Pollution
Degree 2 environment must control conductive pollution and the possibility of
condensation or high humidity. Consideration must be given to the enclosure,
the correct use of ventilation, thermal properties of the equipment and the
relationship with the environment.
Always use this product in the manner specied or the protection provided by
the product may be impaired.
Provide a disconnect device to disconnect the meter from the supply source.
Place this device in close proximity to the equipment and within easy reach
of the operator, and mark it as the disconnecting device. The disconnecting
device shall meet the relevant requirements of IEC 60947-1 and IEC 60947-3
and shall be suitable for the application. In the US and Canada, disconnecting
fuse holders can be used. Provide overcurrent protection and disconecting
device for supply conductors with approved current limiting devices suitable for
protecting the wiring. If the equipment is used in a manner not specied by the
manufacturer, the protection provided by the device may be impaired.
FCC PART 15 INFORMATION
NOTE: This equipment has been tested by the manufacturer and found
to comply with the limits for a class B digital device, pursuant to part 15 of
the FCC Rules. These limits are designed to provide reasonable protection
against harmful interference when the equipment is operated in a residential
environment. This equipment generates, uses, and can radiate radio frequency
energy and, if not installed and used in accordance with the instruction
manual, may cause harmful interference to radio communications. Operation
of this equipment in a residential area may cause harmful interference in
which case the user will be required to correct the interference at his own
expense. Modications to this product without the express authorization of the
manufacturer nullify this statement.