PowerLogic
TM
Series EM4000 930-134-01-A.00
Installation Guide 11/2013
2 ©2013 Schneider Electric All Rights Reserved
Table 1: PowerLogic EM4000 series meter specifications
Specification PowerLogic EM4033 meter PowerLogic EM4080 meter
Dimensions Height: 13.125 in. (33.5 cm)
Width: 12 in. (30.5 cm)
Depth: 2.125 in. (5.5 cm)
Height: 13.125 in. (33.5 cm)
Width: 12 in. (30.5 cm)
Depth: 2.125 in. (5.5 cm)
Weight 8.77 lb (3.98 kg) 8.77 lb (3.98 kg)
Sense voltage 100V to 300V 50/60Hz
2W+N+Protective Earth Wye
3W+N+Protective Earth Wye
3W+Protective Earth Delta
100V to 300V 50/60Hz
2W+N+Protective Earth Wye
3W+N+Protective Earth Wye
3W+Protective Earth Delta
Control voltage and current North America:
• 120V 125 mA 60 Hz
• 277V 54 mA 60 Hz
North America:
• 120V 125 mA 60 Hz
• 277V 54 mA 60 Hz
Current transformers
Measurement Category III
0.333 V secondary CT
Note: All CTs used with the product
must be UL recognized/listed.
80 mA secondary CT
200 A primary CT
Meter burden: 4.04 ohms
CT burden: 20 ohms
Part number: METSECT80200
Note: All CTs used with the product
must be UL recognized/listed.
Measurement accuracy
(Accuracy compliant when used
with 0.3% CTs)
ANSI C12.20 Class 0.5
IEC 62053-22 Class 0.5S
ANSI C12.20 Class 0.5
IEC 62053-22 Class 0.5S
Measurement Canada Approved
EG07 compliant
Pulse inputs 1 and 2 Dry form A and solid-state form A
compatible
Internal 3.3 V pull-up
Maximum frequency 10 Hz
Minimum pulse width 20 ms
Dry form A and solid-state form A
compatible
Internal 3.3 V pull-up
Maximum frequency 10 Hz
Minimum pulse width 20 ms
Non-volatile memory storage 120 days in 15-minute intervals 120 days in 15-minute intervals
Onboard Ethernet port 10/100 Mb/s 10/100 Mb/s
Onboard Modbus RTU serial port RS422 or RS485 19200/9600 Baud RS422 or RS485 19200/9600 Baud
Fuse rating (F1) North America:120V: T125 mA, 250V North America:120V: T125 mA, 250V
Environmental
Operating temperature -40 to 70
o
C -40 to 70
o
C
Operating humidity 5% to 90% non-condensing 5% to 90% non-condensing
Usage environment Indoor or enclosed outdoor environment Indoor or enclosed outdoor environment
Maximum altitude 9843 ft (3000 m) 9843 ft (3000 m)
Pollution degree 2 2
Installation Category II II
Measurement Category III III