Schneider Electric EM4000 Marine Instruments User Manual


 
PowerLogic
TM
Series EM4000 930-134-01-A.00
Installation Guide 11/2013
22 ©2013 Schneider Electric All Rights Reserved
To connect the 5A CT to the converter on the PowerLogic EM4080, follow these
steps:
1. Connect the X1 lead of the 5A CT to the shorting device.
2. Connect the X2 lead of the 5A CT to the shorting device.
3. Connect the X1 lead (red) from the 5A side of the converter to the CT X1 lead on
the shorting device.
4. Connect the X2 lead (black) from the 5A side of the converter to the CT X2 lead
on the shorting device.
5. Connect the X1 lead (white) from the 80mA side of the converter to the X1 lead
within the 25 pair cable for the selected meter point ID listed in Table 2.
6. Connect the X2 lead (black) from the 80mA side of the converter to the X2 lead
within the 25 pair cable for the selected meter point ID listed in Table 2
Figure 12 shows a 5A CT connected to the converter.
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
Turn off all power supplying this equipment before working on or
inside the equipment.
Always use a properly rated voltage sensing device to confirm the
power is off.
NEVER open circuit a CT; use the shorting block to short circuit the
leads of the CT before removing the connection from the meter.
Do not crimp the insulation when making the wire connections.
Failure to follow these instructions will result in death or
serious injury.