PARAMETERS
4
<Setting>
Refer to the figure below and set the corresponding parameters:
When Pr. 43 9999, the Pr. 42 setting applies to forward rotation and the Pr. 43 setting applies to reverse
rotation.
Output Signal
Use Pr. 190 to Pr. 195 to assign the terminals used to output the FU2 and FU3 signals.
4.2.20 Second/third stall prevention (Pr. 48, Pr. 49, Pr. 114, Pr. 115)
Pr. 48 "second stall prevention operation current"
Pr. 49 "second stall prevention operation
frequency"
Pr. 114 "third stall prevention operation
current"
Pr. 115 "third stall prevention operation
frequency"
z The stall prevention operation level can be changed within the range from 0Hz to the frequency set in
Pr. 49 or Pr. 115.
z The stall prevention operation level can be changed by switching the external input signal on-off.
Parameter Number Output Signal
42
FU
43
50 FU2
116 FU3
Note: 1. When the plug-in option unit is used to exercise encoder feedback control, use the RUN (running)
signal. (If the FU, FU2 or FU3 signal is used, the brake may not be opened.)
2. Changing the terminal assignment with any of Pr. 190 to Pr. 195 may affect the other functions.
Make setting after checking the functions of the corresponding terminals.
Parameter
Number
Factory Setting Setting Range
48 150% 0 to 200%
49 0 0 to 400Hz, 9999
114 150% 0 to 200%
115 0 0 to 400Hz
Pr.50
Pr.42
Pr.116
Pr.50
Pr.43
Pr.116
Output signal
FU,FU2,FU3
Output frequency (Hz)
Forward
rotation
Reverse
rotation
Time
OFF OFF OFFON ON
Pr. 44, Pr. 45 Refer to Pr. 7.
Pr. 46 Refer to Pr. 0.
Pr. 47 Refer to Pr. 3.
Related parameters
Pr. 22 "stall prevention operation level"
Pr. 23 "stall prevention operation level
compensation factor at double
speed"
Pr. 66 "stall prevention operation level
reduction starting frequency"
Pr. 154 "voltage reduction selection
during stall prevention operation"
Pr. 180 to Pr. 186
(input terminal function selection)
Running frequency
Stall prevention
operation current
Acceleration
Deceleration/constant speed
Pr.49
Pr.115
Pr.114
Pr.48