A SERVICE OF

logo

160
PARAMETERS
<Setting>
Refer to the following list and set the parameters:
*: When Pr. 59 = "1 or 2", Pr. 79 = "5", and Pr. 270 = "1 or 3", the functions of the RL, RM, RH and RT signals change as listed above.
**: Operated when the relay contact "opens".
Setting
Signal
Name
Functions Relevant Parameters
0RL
Pr. 59 = 0 Low-speed operation command
Pr. 4 to Pr. 6
Pr. 24 to Pr. 27
Pr. 232 to Pr. 239
Pr. 59 = 1, 2 * Remote setting (setting clear) Pr. 59
Pr. 79 = 5 *
Programmed operation group
selection
Pr. 79, Pr. 200, Pr. 201 to Pr. 210, Pr. 211
to Pr. 220, Pr. 221 to Pr. 230, Pr. 231
Pr. 270 = 1, 3 Stop-on-contact selection 0 Pr. 270, Pr. 275, Pr. 276
1RM
Pr. 59 = 0 Middle-speed operation command
Pr. 4 to Pr. 6, Pr. 24 to Pr. 27, Pr. 232 to
Pr. 239
Pr. 59 = 1, 2 * Remote setting (deceleration) Pr. 59
Pr. 79 = 5
Programmed operation group
selection
Pr. 79, Pr. 200, Pr. 201 to Pr. 210, Pr. 211
to Pr. 220, Pr. 221 to Pr. 230, Pr. 231
2RH
Pr. 59 = 0 High-speed operation command
Pr. 4 to Pr. 6, Pr. 24 to Pr. 27, Pr. 232 to
Pr. 239
Pr. 59 = 1, 2 Remote setting (acceleration) Pr. 59
Pr. 79 = 5
Programmed operation group
selection
Pr. 79, Pr. 200, Pr. 201 to Pr. 210, Pr. 211
to Pr. 220, Pr. 221 to Pr. 230, Pr. 231
3RT
Second function selection (Note 7) Pr. 44 to Pr. 50
Pr.270 = 1, 3 * Stop-on-contact selection 1 Pr. 270, Pr. 275, Pr. 276
4 AU Current input selection Refer to page 13
5 JOG Jog operation selection Pr. 15, Pr. 16
6 CS Automatic restart after instantaneous power failure selection Pr. 57, Pr. 58, Pr. 162 to Pr. 165, Pr. 611
7OH
External thermal relay input**
The externally provided overheat protection thermal relay,
motor-embedded temperature, etc. is operated to stop the
inverter.
Refer to page 196
8 REX 15-speed selection (combination with RL, RM, RH)
Pr. 4 to Pr. 6, Pr. 24 to Pr. 27,
Pr. 232 to Pr. 239
9 X9 Third function Pr. 110 to Pr. 116
10 X10 FR-HC, FR-CV connection (inverter operation enable) Pr. 30, Pr. 70
11 X11
FR-HC connection (instantaneous power failure detection)
(Only when FR-A5NR option is fitted)
Pr. 30, Pr. 70
12 X12 PU operation external interlock Pr. 79
13 X13 External DC injection brake start Pr. 10 to Pr. 12
14 X14 PID control valid terminal Pr. 128 to Pr. 134
15 BRI Brake opening completion signal Pr. 278 to Pr. 285
16 X16 PU-external operation switch-over Pr. 79
17 X17 Load pattern selection forward/reverse rotation boost Pr. 14
18 X18
Advanced magnetic flux vector-V/F switch-over (V/F control is
executed when X18 is on)
Pr. 80, Pr. 81, Pr. 89
19 X19 Load torque high-speed frequency Pr. 271 to Pr. 274
20 X20
S-pattern acceleration/deceleration C switch-over terminal
(only when FR-A5AP option is fitted)
Pr. 380 to Pr. 383
22 X22
Orientation command (Note 8) (only when FR-A5AP option is
fitted)
Pr. 350 to Pr. 369
23 LX Pre-excitation (Note 9) (only when FR-A5AP option is fitted) Pr. 80, Pr.81, Pr. 359, Pr. 369, Pr. 370
9999 No function