167
PARAMETERS
4
<Setting procedure>
(Example: Set point No. 1, forward rotation, 30Hz, 4 hours 30 minutes)
1) Read Pr. 201 value.
2) Enter "1" (forward rotation) in Pr. 201 and press the key ( key when using the FR-PU04
parameter unit).
3) Enter 30 (30Hz) and press the key ( key when using the FR-PU04 parameter unit). (Note 1)
4) Enter "4.30" and press the key ( key when using the FR-PU04 parameter unit). (Note 2)
5) Press the key to move to the next parameter (Pr. 202), and press the key ( key when using
the FR-PU04 parameter unit) to display the current setting. Hereafter, press the key to advance the
parameter one by one.
Assuming that operation has been programmed as indicated in the following table, the operation pattern is
as shown in the figure below:
<Operation pattern>
(4) Input signals
(5) Output signals
Note: 1. To make a stop, write "0" in the rotation direction and frequency. Set "9999" for no setting.
2. An error will result if 4.80
is entered (59 minutes or 59 s is exceeded).
No. Operation Parameter Setting
1 Forward rotation, 20Hz, 1 hours 0 minute Pr. 201 = 1, 20, 1:00
2 Stop, 3 hours 0 minutes Pr. 202 = 0, 0, 3:00
3 Reverse rotation, 30Hz, 4 hours 0 minutes Pr. 203 = 2, 30, 4:00
4 Forward rotation, 10Hz, 6 hours 0 minutes Pr. 204 = 1, 10, 6:00
5 Forward rotation, 35Hz, 7 hours 30 minutes Pr. 205 = 1, 35, 7:30
6 Stop, 9 hours 0 minute Pr. 206 = 0, 0, 9:00
Name Description Signal Level Remarks
Group signal
RH (group 1)
RM (group 2)
RL (group 3)
Used to select the group for programmed
operation.
Photocoupler isolated
May also be driven by
transistor.
When ic = 10mA, Vec<0.5V
should be satisfied.
Timer reset signal (STR) Input to zero the reference time of day.
Programmed operation start
signal (STF)
Input to start programmed operation.
Name Description Signal Level Remarks
Time-out signal (SU)
Output on completion of the operation of
the selected group and cleared on timer
reset.
Open collector output
(isolated)
Permissible load
24VDC, 0.1A
Only when Pr. 76 = 3
Group select signals
(FU, OL, IPF)
Output during running of corresponding
group's program and cleared on timer
reset.
SET
WRITE
SET
WRITE
SET
WRITE
SET
READ
20Hz
01 3
4
6
9
10Hz
32456
7:30
35Hz
Time of day
Set point 1
Forward
rotation