126
PARAMETERS
Note: 1. Underlined parameter values are values changed from the factory settings.
2. The motor constants indicate the data measured in the offline auto tuning.
3. The Pr. 85 settings of "9999" (factory setting) and "10" are equal.
4. Wrong setting will provide an alarm output. Therefore, make sure that the settings are correct.
5. For the output is 0.2kW, set Pr. 80 "motor capacity " to 0.4 (kW).
• When offline auto tuning is not enabled
(When the inverter capacity is one rank higher than the motor capacity)
1) Set Pr. 9 "electoronic thermal O/L relay", Pr. 80 "motor capacity", Pr. 81 "number of motor poles", Pr. 83
"rated motor voltage" Pr. 84 "rated motor frequency" according to the motor.
2) Set "14" in Pr. 71 and "801" in Pr. 77.
3) Set the values in the table on the previous page in Pr. 85, Pr. 86, Pr. 89 and Pr. 94.
4) Calculate the Pr. 82 setting using the following calculation expression.
5) Calculate the Pr. 90 to Pr. 93 setting using the following calculation expression.
6) Set "1" in Pr. 95
7) Return the Pr. 77 setting to the original value.
(Note) When using the 0.4K inverter and the 0.2K motor, enter the values in the table on the previous page.
Pr.82
setting value
=
Tuning value with the same capacity
(Refer to table on the previous page)
×
Rated current (A) of the inverter equal to the motor in capacity
Rated current (A) of the inverter one rank higher than the motor
Pr.90 to Pr. 93
setting value
=
Tuning value with the same capacity
(Refer to table on the previous page)
×
Rated current (A) of the inverter one rank higher than the motor
Rated current (A) of the inverter equal to the motor in capacity
Calculation expression example 1
for Pr.82, Pr.90 to Pr.93
Combination Inverter : FR-A520-2.2K (Rated current value 11 [A])
Motor : SF-HR 1.5kW 4P
Parameter
Setting value for a combination of motor with
one rank higher in capacity inverter.
Conversion calculation method for a combination of
motor one rank higher in capacity inverter.
85 10(9999)(*) No calculation
86 130(*) No calculation
89 100(*) No calculation
82 1786 2456(*) × (8[A] / 11[A]) = 1786
90 1216 884(*) × (11[A] / 8[A]) = 1216
91 1240 902(*) × (11[A] / 8[A]) = 1240
92 1584 1152(*) × (11[A] / 8[A]) = 1584
93 1584 1152(*) × (11[A] / 8[A]) = 1584
94 790(*) No calculation
Rated current value for the FR-A520-1.5K.
Values (*) are setting values (SF-HR 1.5kW) in the table on the previous page.
Calculation expression example 2
for Pr. 82, Pr. 90 to Pr.93
Combination Inverter : FR-A540-2.2K (Rated current value 6 [A])
Motor : SF-HRCA 1.5kW 4P
Parameter
Setting value for a combination of the motor and
the inverter one rank higher in capacity.
Conversion calculation method for a combination of
the motor and the inverter one rank higher in capacity.
85 10(9999)(*) No calculation
86 130(*) No calculation
89 100(*) No calculation
82 1643 2465(*) × (4[A] / 6[A]) = 1643
90 1340 893(*) × (6[A] / 8[A]) = 1340
91 1370 913(*) × (6[A] / 4[A]) = 1370
92 1740 1160(*) × (6[A] / 4[A]) = 1740
93 1740 1160(*) × (6[A] / 4[A]) = 1740
94 796(*) No calculation
Rated current value for the FR-A540-1.5K.
Values (*) are setting values (SF-HRCA 1.5kW) in the table on the prrevious page.
Pr. 89 Refer to Pr. 80.