A SERVICE OF

logo

165
PARAMETERS
4
4.2.54 Programmed operation function (Pr. 200 to Pr. 231)
Pr. 200 "programmed operation minute/second
selection"
Pr. 201 to Pr. 210 "program set 1 1 to 10"
Pr. 211 to Pr. 220 "program set 2 11 to 20"
Pr. 221 to Pr. 230 "program set 3 21 to 30"
Pr. 231 "timer setting"
In programmed operation, automatic operation is performed under the control of the internal timer in
accordance with the preset time of day, running frequency and rotation direction.
zThis function is made valid when the following parameter is set to the following value:
Pr. 79 = "5" (programmed operation)
zYou can select the time unit for programmed operation between "minute/second" and "hour/minute".
zThe start time of day, rotation direction and running frequency are defined as one point and every 10 points
are grouped into three:
Group 1: Pr. 201 to Pr. 210
Group 2: Pr. 211 to Pr. 220
Group 3: Pr. 221 to Pr. 230
zUse Pr. 231 to set the time of day when programmed operation is started.
<Wiring example>
For sink logic
Parameter
Number
Factory Setting Setting Range Remarks
200 0 0 to 3
0, 2 [minute/second]
1, 3 [hour/minute]
201 to 210 0, 9999, 0
0 to 2
0 to 400, 9999
0 to 99.59
0 to 2: Rotation direction
0 to 400, 9999: Frequency
0 to 99.59: Time
211 to 220 0, 9999, 0
0 to 2
0 to 400, 9999
0 to 99.59
0 to 2: Rotation direction
0 to 400, 9999: Frequency
0 to 99.59: Time
221 to 230 0, 9999, 0
0 to 2: Rotation direction
0 to 400, 9999:
Frequency
0 to 99.59: Time
0 to 2: Rotation direction
0 to 400, 9999: Frequency
0 to 99.59: Time
231 0 0 to 99.59
Related parameters
Pr. 76 "alarm code output selection"
Pr. 79 "operation mode selection"
STF
RH
RM
RL
STR
SD
FU
OL
PF
SU
SE
I
1
2
3
U,V,W
Output signal common
Programmed
operation start
Group selection
Timer reset
Input signal common
Inverter
Motor
Terminal function Pr. 79 = 5
Terminal function Pr. 76 = 3
Group run signals
(Open collector)
Time-out signal
R,S,T