A SERVICE OF

logo

171
PARAMETERS
4
4.2.57 Output phase failure protection selection (Pr. 251)
Pr. 251 "output phase failure protection selection"
You can make the output phase failure protection (E.LF) function which stops the inverter output invalid if one
of the three phases (U, V, W) on the inverter's output side (load side) becomes open.
4.2.58 Override bias/gain (Pr. 252, Pr. 253)
Pr. 252 "override bias"
Pr. 253 "override gain"
You can extend the 50% to 150% override range (to 0% to 200%), which is covered when Pr. 73 "0 to 5V, 0
to 10V selection" is used to select the override, and set the override value as desired.
Parameter
Number
Setting
Range
Minimum
Setting
Increments
Factory Setting Description
251 0,1 1 1
0: Without output phase failure protection
1: With output phase failure protection
Parameter Number Setting Range
Minimum Setting
Increments
Factory Setting
252 0 to 200% 0.1% 50%
253 0 to 200% 0.1% 150%
Related parameters
Pr. 73 "0 - 5V / 0 - 10V selection"
Override value (%)
Pr. 252
0V 2.5V
(5V)
5V
(10V)
0
50
100
150
200
Factory setting
(50% to 150%)
Voltage across 2-5
Pr. 253