Mitsubishi Electronics FR-E5NC Marine Battery User Manual


 
INVERTER SETTING
13
(2) Operation mode switching method
Change the operation mode as described below:
C
D
A
B
E
F
CC-Link
Switched by
PC program
External
operation
Switched
from PU
PU operation
(Switching disallowed)
Symbol Switching Type Switching Method
A PU operation
External operation Operate the external operation key on the PU.
B External operation
PU operation Operate the PU operation key on the PU.
C External operation
CC-Link operation By the user program of the PLC.
D CC-Link operation
External operation By the user program of the PLC.
E PU operation
CC-Link operation
Switching disallowed. Allowed if external operation is selected in A
and CC-Link operation is then selected in C.
(Note 2)
F CC-Link operation
PU operation
Switching disallowed. Allowed if external operation is selected in D
and PU operation is then selected in B.
(Note 2)
When "1" is set in Pr. 340 "link start mode selection", the operation mode is CC-Link operation at power on or inverter
reset.
Note: 1. When setting "1" in Pr. 340, the initial settings (station number setting, etc.) of the inverter must be made
without fail.
2. In the switch-over mode (Pr. 79 = 6), switching in E and F is allowed.