Mitsubishi Electronics FR-E5NC Marine Battery User Manual


 
FUNCTION OVERVIEW
20
4.2 Setting the Running Frequecy
The following table lists the functions which can be executed from the programmable logic controller in the CC-Link system:
Operation Mode
Control Location Item
PU operation External operation CC-Link operation
Operation command Disallowed Disallowed Allowed
Running frequency setting Disallowed Disallowed Allowed
Monitoring Allowed Allowed Allowed
Parameter write Disallowed (*3) Disallowed (*3) Allowed (*3)
Parameter read Allowed Allowed Allowed
Inverter reset Disallowed Disallowed Allowed (*1)
Error reset at inverter fault
(RY1A)
Allowed (*1) Allowed (*1) Allowed (*1)
User program
Stop command (*2) Disallowed Disallowed Allowed
Inverter reset terminal Allowed Allowed Allowed
Operation command Disallowed Allowed Allowed (*4)
Control circuit
terminal
Frequency setting Disallowed Allowed Allowed (*4)
(
*
1) At occurrence of a communication error, the inverter cannot be reset from the computer. (For inverter reset, refer
to the inverter manual.)
(
*
2) As set in Pr. 75.
(
*
3) As set in Pr. 77.
Values can be written to Pr. 4 to Pr. 6, Pr. 22, Pr. 24 to Pr. 27, Pr. 52 to Pr. 56, Pr. 72, Pr. 232 to Pr. 239 during
operation.
(For full information, refer to the inverter manual.)
(
*
4) As set in Pr. 338 and Pr. 339
Note 1. The inverter goes into the external operation mode if it is reset from the PLC in the CC-Link operation mode.
The setting of "1" in Pr. 340 (link start mode) selects CC-Link operation mode.