Mitsubishi Electronics FR-E5NC Marine Battery User Manual


 
PROGRAMMING EXAMPLES
44
6.10 Program Example for Resetting the Inverter at Inverter Error
1) The following program resets the inverter of station 2.
M9036
FROM 0000
H
00E2
H
M200 2
K
SET M126
26
X0000 X000F X0001 M226
K4
36
Reads the remote input (RX20 to RX3F)
data of buffer memory to M200-M231.
X0020
Write setting
SET M302
RST M302
M302
TO 0000
H
0162
H
M100
K4
2
K
M9036
87
43
Writes M100-M131 data to the remote outputs
(RY20 to RY3F) of buffer memory.
M226
Switches on the error reset request flag (RY1A).
Switches off the error reset request fla
g
(
RY1A
)
if the error status flag (RX1A) is off.
RST M126
Note: 1. The above inverter reset using RY1A may be made only when an inverter error occurs.
Also, inverter reset can be made independently of the operation mode.
2. When using the instruction code execution request (RYF) with the instruction code (FD
H
) and data (9696
H
)
to reset the inverter, set "1" in Pr. 341 "link start mode" (refer to page 14) or change the operation mode to
the CC-Link operation mode. (For the program example, refer to page 34.)